Home > Products > Power Energy Solution > Emergency Power Supply

China Emergency Power Supply Manufacturers, Suppliers, Factory

Shangyu (Shenzhen) Technology Co., Ltd. (www.cpsypower.com) specializes in various specifications of UPS power supplies, precision air conditioners, charging piles, EPS emergency power supplies, etc. The company has 3C fire protection certification and has obtained more than 70 soft certificates. 100 invention patent certificates. It is a national high-tech enterprise and a Shenzhen technology-based small and medium-sized enterprise. For more than 10 years, Shangyu has been adhering to the business philosophy of conquering customers with quality, impressing customers with price, moving customers with service, and winning customers with trust. The market share of Shangyu products has increased by 5% year by year. Shangyu is willing to cooperate with you for a win-win situation. , create brilliance together!


The EPS emergency power supply set up according to specific needs is advanced and practical in the fire power supply industry. It can realize microcomputer monitoring and processing, and can be used for fire emergency lighting, emergency mercury lamps, fire elevators, water pumps, smoke exhaust fans and other fire protection facilities. Automatic control. EPS uninterruptible power supply provides emergency lighting power supply for important places such as high-rise buildings, telecommunications network rooms, hospitals, financial centers, civil aviation airports, exhibition venues, theaters, government offices, subways and light rails, commercial real estate, petrochemicals, shopping malls and supermarkets.


The EPS emergency power system mainly includes rectifier charger, battery pack, inverter, mutual switching device and system controller. Among them, the inverter is the core. DSP or single-chip CPU is usually used to perform SPWM modulation control on the inverter part to obtain a good AC waveform output. The function of the rectifier charger is to realize timely charging of the battery pack when the mains input is normal. Charging; the function of the inverter is to convert the DC power stored in the battery pack into AC output when the mains power is abnormal, supplying stable and continuous power to the load equipment; the mutual switching device ensures that the load is between the mains power and the inverter output. Smooth switching; the system controller controls the entire system in real time, and can send out fault alarm signals and receive remote linkage control signals, and can realize remote monitoring of the EPS system from the host computer through standard communication interfaces.


The basic working principle of EPS is:

⑴ When the mains power input is normal, the input mains power supplies power to important loads through the mutual switching device. At the same time, the system controller automatically detects the mains power and manages the charging of the battery pack through the charger. Usually the capacity of the EPS charger is only equivalent to 10% of the battery pack capacity (Ah). It only needs to provide the battery pack float charge or supplementary power function, and does not need to have the ability to directly provide DC power to the inverter. At this time, the mains power supplies power to the user's emergency load through the mutual switching device in the EPS. At the same time, under the control of the EPS system controller, the inverter stops working and automatically shuts down. The user load actually uses the grid power supply at this time. At this time, it is usually said that the EPS emergency power supply is in a sleep state, which can effectively achieve the effect of energy saving.

⑵ When the input mains power supply is interrupted or the mains voltage exceeds the limit (±15% or ±20% of the rated input voltage), the system controller commands the mutual switching device to switch to the inverter within a short period of (0.1~4) S The EPS system supplies power to user loads with the support of DC energy provided by the battery pack.

⑶ When the input mains voltage returns to normal operation, the EPS system controller issues an instruction to shut down the inverter, and also performs a switching operation from the inverter power supply to the AC bypass power supply through the mutual switching switch. After that, the EPS provides mains power to the load through the AC bypass power supply path, and at the same time continues to charge its battery pack through the rectifier charger.


EPS power supply is mainly used in energy-saving power supply, building lighting, road traffic lighting, tunnel lighting, electric power, industrial and mining enterprises, fire elevators, fire pumps and other scenarios. At present, the emergency power supply (EPS) provided by Shangyu CPSY can be divided into powered EPS, lighting EPS and hybrid EPS according to different load conditions. The following are the differences between the three:

Item Illuminated EPS Power EPS Hybrid EPS
Loading condition 500W-100KW 2.2KW-200KW 2.2KW-400KW
Power supply mode Centralized power supply Centralized power supply Centralized power supply
Characteristic performance Latest IGBT inverter technology Reduce the impact current by 4-7 times when starting up, variable frequency start function The latest IGBT inverter + pulse width modulation PWM technology
Output waveform sine wave SPWM wave SPWM wave
Fire linkage Can Can Can
Service life 10 years 10 years+ 20 years
Unattended Can Can Can
Transfer time <5s <0.25s <0.25s
Input voltage 220Vac or 380Vac 380Vac 380Vac
The output voltage 220Vac 380Vac 380Vac
Isolation transformer Yes, output side Yes, output side Yes, output side
circuit protection 5 types, short circuit protection, overvoltage/overcurrent/overload/overtemperature protection 5 types, short circuit protection, overvoltage/overcurrent/overload/overtemperature protection 5 types, short circuit protection, overvoltage/overcurrent/overload/overtemperature protection
Main components Using internationally renowned brands with high reliability Using internationally renowned brands with high reliability Using internationally renowned brands with high reliability
scenes to be used Various lamps, halogen lamps, sodium lamps, etc. Various power loads, fire elevators, rolling shutter doors, water pumps, fans, motors, etc. Various lamps and various power loads, elevators, central air conditioners, fire pumps, etc.

The emergency power supply provided by Shangyu CPSY has passed CE, UL and other certifications and meets the requirements of relevant international standards. It also proves the company's R&D and production capabilities. Our emergency power supply products are widely used in data centers, communication rooms, hospitals, schools, shopping malls and other important places, and have won unanimous praise from our customers. We are guided by customer needs, driven by technological innovation, and based on quality service, and are committed to becoming a leader in the emergency power and backup power industry at home and abroad.

We cooperate with well-known brands such as APC, Powerware, MGE, ETL, etc., and have high visibility and market share in the power supply field. Our products are widely used in data centers, communication equipment rooms, hospitals, schools and other important places. Our main exports of emergency power supplies include the United States, the United Kingdom, France, Germany, Australia, India, Brazil, Mexico and other countries. These countries have a large demand for emergency power supplies and also have high requirements for the performance and quality of emergency power supplies. Require.


Shangyu EPS emergency power supply is widely used in emergency lighting and fire-fighting facilities, as well as in other fields, such as industry, medical care, public facilities, etc. It can be used in various occasions that require stable power supply. Its advantages and disadvantages are mainly as follows :

Advantage:

1. Quick response: Emergency power supply usually has quick response capability and can start and supply power in a short time.

2. When the power grid is powered, it is static and noise-free; when power is supplied, the noise is less than 60dB. It does not require smoke exhaust and earthquake-proof treatment, and is energy-saving, pollution-free, and has no fire hazards;

3. Automatic switching can achieve unattended operation. The switching time between grid power supply and EPS power supply is 0.1~0.25s;

4. Strong load capacity, EPS is suitable for inductive, capacitive, and comprehensive load equipment, such as elevators, water pumps, fans, office automation equipment, emergency lighting, etc.;

5. Reliable in use, the host has a long life of 10-20 years;

6. Adapt to harsh environments. It can be placed in the basement or distribution room, or it can be installed close to the emergency load site to reduce power supply lines.

shortcoming:

1. High maintenance cost: Emergency power supply requires regular maintenance and inspection to ensure its normal operation, which requires a certain cost.

2. Limited life: The battery life of emergency power supply is usually limited, and the battery needs to be replaced or maintained regularly.

3. Larger weight and volume: Emergency power supplies are usually larger in weight and volume, making them less suitable for portability.

4. Can only be used in emergencies: The emergency power supply can only be used in emergency situations and cannot be used as a power supply for daily use.


Shangyu EPS power supply refers to an emergency power supply that inverts the DC power of the battery into AC power. It is suitable for loads that allow power interruption time of more than 0.25s, which is simpler than UPS. The UPS power supply protects data loss and equipment damage during power outages. The difference between EPS and UPS is as follows:

Item EPS power supply UPS power supply
Capacity 0.5KVA-200KVA 0.5KVA-2000KVA
Product cost Lower Higher, about 2 times EPS
Output accuracy Generally Higher
Service life 10-20 years 8-10 years
Transfer time 0.1s-0.5s 0ms-10ms
Machine efficiency 80% 90%
Stability Generally High
Soft start Frequency conversion Fixed frequency
Maintenance management High, requiring regular manual inspection and maintenance Low, intelligent management
Usage Sleep normally and activate only in emergencies Daily use
circuit protection 5 types, short circuit protection, overvoltage/overcurrent/overload/overtemperature protection 9 types, leakage/short circuit protection, anti-interference, phase loss/undervoltage/overvoltage/overcurrent/overload/overtemperature protection, etc.
Other Functions None Automatic voltage stabilization function, frequency stabilization function
Output waveform Sine wave or SPWM wave square wave or sine wave
Classification Power EPS, lighting EPS and hybrid EPS Industrial UPS, commercial UPS, household UPS
Load function Diesel generator sets Only industrial frequency machines can be equipped with diesel generator sets
Adopt technology The latest IGBT inverter + pulse width modulation PWM technology Double conversion technology + latest IGBT inverter + pulse width modulation PWM technology
Common ground Simple structure, low cost, low energy consumption and no noise, long host life Simple structure, small size, low cost, wide input voltage range, low noise
Application scenarios Emergency power supply for road traffic lighting, venue lighting, building fire escape lighting, fire pumps, sprinkler pumps and other fire protection equipment Provide backup power for key equipment such as valve systems, computers, EPS, PLC, DCS, control room system power supplies, motor protection, servers, IT equipment, weak current system power supplies, relay protection, and motor protection.
Because EPS emergency power products are products that change with different design needs, the following explanations should be made for each specification and variety when purchasing:

1) The number of input channels, whether it is dual-channel power input or single-channel power input;

2) Enter the number of phases, whether it is single-phase or three-phase;

3) Total load capacity refers to the total load capacity of an EPS emergency power supply;

4) Load type, refers to whether it is used for lighting or power, and what load it carries;

5) Emergency backup time;

6) The number of output branches refers to how many loops are required to be output;

7) Whether fire linkage and the number of branches are required;

8) The location and method of the incoming and outgoing wires and the size of the incoming and outgoing wire holes refer to whether there are any special requirements for the incoming and outgoing wires;

9) Other requirements refer to any requirements other than the above requirements.


View as  
 
<>
CPSY is a professional Emergency Power Supply manufacturers and suppliers in China, known for our excellent service and reasonable prices. As a factory, we can make customized Emergency Power Supply. All our products meet CE, ROHS, ISO9001 standards, etc. If you are interested in our easy-maintainable and durable Emergency Power Supply, please contact us. We sincerely hope to become your reliable long-term business partner!
We use cookies to offer you a better browsing experience, analyze site traffic and personalize content. By using this site, you agree to our use of cookies. Privacy Policy
Reject Accept